hose stream allowance

15:46 Dec 17, 2018
English to Italian translations [PRO]
Tech/Engineering - Engineering: Industrial / Fire Protection/Antincendio
English term or phrase: hose stream allowance
The minimum water demand requirements for a sprinkler system shall be determined by adding the hose stream allowance to the water demand for sprinklers.

Il contesto è quello di un calcolo idraulico riferito in particolare ad un impianto antincendio. In particolare è un'estratto da norma americana NFPA.

Inoltre vorrei sapere che significato ha hose allowance.

Grazie
Laura Gentili
Italy
Local time: 19:35


Summary of answers provided
2tolleranza sulla portata di flusso rete idrante
martini


  

Answers


16 hrs   confidence: Answerer confidence 2/5Answerer confidence 2/5
tolleranza sulla portata di flusso rete idrante


Explanation:
questa è la mia ricerca e la mia proposta in base a tutto quello che ho letto

ricerca in base ai dati
hose stream allowance of 250 gpm .....

qui si fa più volte rif. alla norma NFPA

Portata nominale di flusso:
2” (DN50): 0 - 250 GPM (0 - 946 l/min)
3” (DN80): 0 - 550 GPM (0 - 2080 l/min)
https://www.tyco-fire.com/TFP_translate/TFP1580_IT.pdf

Distribution System Requirements for Fire Protection
https://books.google.it/books?isbn=0898679354
1998 - ‎Technology & Engineering
Required fire flow for sprinklered properties consists of the flow required for sprinklers, including a hose-stream allowance or 500 gpm (31.5 L/s),

The Whys Behind FM Global Data Sheets 2-0 and 8-9 - SFPE
https://www.sfpe.org/page/2012_Q2_4?
*****The design of 8 @ 40 (2.8) has a hose stream allowance of 250 gpm (950L/min) and a duration of 60 minutes when the maximum linear spacing is up to 12 ...

Inoltre pressioni elevate sulle reti idranti possono dar luogo alla ingestibilità della manichetta e della lancia. .....
le tolleranze sulla prevalenza e sulla portata .....
La norma NFPA 20, che per le tolleranze prestazionali rimanda alle Hydraulic Instituite,
https://www.edilizianamirial.it/pompe-antincendio-gruppi-di-...

From NFPA 13, 2013:
A.11.4.2
The hose stream demand required by this standard is intended to provide the fire department with the extra flow they need to conduct mop-up operations and final extinguishment of a fire at a sprinklered property. This is not the fire department manual fire flow, which is determined by other codes or standards. However, it is not the intent of this standard to require that the sprinkler demand be added to the manual fire flow demand required by other codes and standards.
That should explain pretty well what the hose stream allowance is.
https://www.eng-tips.com/viewthread.cfm?qid=356133

martini
Italy
Local time: 19:35
Specializes in field
Native speaker of: Italian
PRO pts in category: 96
Login to enter a peer comment (or grade)



Login or register (free and only takes a few minutes) to participate in this question.

You will also have access to many other tools and opportunities designed for those who have language-related jobs (or are passionate about them). Participation is free and the site has a strict confidentiality policy.

KudoZ™ translation help

The KudoZ network provides a framework for translators and others to assist each other with translations or explanations of terms and short phrases.


See also:
Term search
  • All of ProZ.com
  • Term search
  • Jobs
  • Forums
  • Multiple search